<p>GENERAL TECHNICAL SPECIFICATIONS<br />
1.-The conductors shall be unipolar wire, electrolytic copper, with thermo-plastic insulation of type TW for 600 volts in incoming circuits and type TW in the interior distribution of the INDECO, O PIRELLI brands, the conductors of minimum caliber to be used in lighting and Power socket will be No. 14.<br />
2.- Pipes will be made of polyvinyl chloride of the PVC-SAP heavy standard type in connections and up to the distribution boards, the diameters of the tubes are indicated in the drawings<br />
3.- The Board will be used to build a special factory cabinet, with automatic thermo-magnetic interrupters of the NO-FUSE type.<br />
The dimensions of the cabinet for the board will be given in the house suppliers<br />
4.- The Outlets and Switches will be built-in, similar to the Ticino of the series<br />
LIVING OR MAGIC with aluminum plate, as indicated by the owner<br />
5.- In the circuits of Telephone and cable TV will be with wire guide No. 16 in all the<br />
conduits this same specification will be valid in intercom circuits if not installed by the constructor<br />
6, - The cables will be identified according to the following colors:<br />
- Earth Cable = Yellow<br />
- Neutral Cable = White<br />
- Cable for Phases: R = Red, S = Black, T = Green<br />
7.- The boxes will be of galvanized iron of the heavy type, paint with varnish or anticorrosive before wiring<br />
To fix the boxes do not use any mortar based on plaster<br />
The phase boxes have a blind cover, secured with a "STOWBOLT" screw<br />
8.- In lighting fixtures, the cables will be THHW<br />
9.- To join the pipes to the boxes, use PVC connectors<br />
10.- In the lighting lines or electrical outlets, the number of rays indicates the number of conductors passing through the pipes</p>